New Franklin Inspection and Maintenance ordinance (§ 700.140)
Chapter 700: Water Regulations · Article II. Cross-Connection Control
In short: Customers with required backflow devices must have them inspected and tested, at least every 12 months for air-gap separations and double-check valve assemblies.
Our plain-English summary, not the official text or legal advice. The ordinance below is what counts.
A. It shall be the duty of the consumer at any premises on which backflow prevention devices required by this Article are installed to have inspections, tests and overhauls made in accordance with the following schedule or more often where inspections indicate a need.
1. Air-gap separation shall be inspected at the time of installation and at least every twelve (12) months thereafter.
2. Double-check valve assemblies shall be inspected and tested every twelve (12) months thereafter. They shall be dismantled, inspected internally, cleaned and repaired whenever needed and at least every thirty (30) months.
3. Reduced pressure principle backflow prevention devices shall be inspected and tested for tightness at the time of installation and at least every twelve (12) months thereafter. They shall be dismantled, inspected internally, cleaned and repaired whenever needed and at least every five (5) years.
B. Inspections, tests and overhauls of backflow prevention devices shall be made at the expense of the water consumer and shall be performed by a State of Missouri certified backflow prevention device tester.
C. Whenever backflow prevention devices required by this Article are found to be defective, they shall be repaired or replaced at the expense of the consumer without delay.
D. The water consumer must maintain a complete record of each backflow prevention device from purchase to retirement. This shall include a comprehensive listing that includes a record of all tests, inspections and repairs. Records of inspections, tests, repairs and overhauls shall be made available to the Water Purveyor upon request.
E. Backflow prevention devices shall not be by-passed, made inoperative, removed or otherwise made ineffective without specific authorization by the Water Purveyor.
Official source: New Franklin City Code, page 18 of the city's PDF