Boonville Backflow prevention assemblies ordinance (§ 21-42.27)
Chapter 21: Waters, Sewers and Solid Waste Disposal · Division 5. Cross-Connection Control
(a) Any backflow prevention assembly required to protect the facilities listed in section 21-42.26(c) shall be of a model or construction approved by the director of public works and the state department of natural resources.
(1) Air gap separation to be approved shall be at least twice the diameter of the supply pipe, measured vertically above the top rim of the vessel, but in no case less than one inch. (2) A double check valve assembly or a reduced pressure principle backflow prevention assembly shall be approved by the director of public works, and shall appear on the current "list of approved backflow prevention assemblies" established by the state department of natural resources.
(b) Existing backflow prevention assemblies approved by the director of public works at the time of installation and properly maintained shall except for inspection and maintenance requirements, be excluded from the requirements of this division so long as the director of public works or authorized representative is assured that they will satisfactorily protect the water system. Whenever the existing assembly is moved from its present location, or requires more than minimum maintenance, or when the director of public works finds that the maintenance constitutes a hazard to health, the unit shall be replaced by a backflow prevention assembly meeting the requirements of this division.
Official source: City of Boonville official Code of Ordinances (online): look up Sec. 21-42.27
Text from Supplement 8 (December 2025), through Ordinance 4678 of December 16, 2024.
Last checked October 30, 2026. The city's official copy controls; this page is a reading copy, not legal advice.